Chengdu Xuguang Electronics Co., Ltd.
Main products:Vacuum Interrupter,Electron Tube
Products
Contact Us
  • Contact Person : Ms. LI YAN
  • Company Name : Chengdu Xuguang Electronics Co., Ltd.
  • Tel : 0086-28-83967045
  • Fax : 0086-28-83967779
  • Address : Sichuan,Chengdu,XINGONG AVENUE 318#, EAST INDUSTRY ZONE,610500 XINDU DISTRICT,
  • Country/Region : China
  • Zip : 610500

vacuum interrupter

vacuum interrupter
Product Detailed
This vacuum interrupter is designed for 24KV-630A-16KA vacuum circuit breakers; for the outline drawing, please contact me NOW.

CERAMIC VACUUM INTERRUPTER FOR CIRCUIT-BREAKER

MAIN TECHNICAL DATA                                         TYPE: TD-24/1250-16B(2211)

Data

Unit

Value

 

Rated Voltage

kV

24

 

Lightning Impulse Withstand Voltage (Peak)

kV

125

 

Short-time (1min) Power-frequency Withstand Voltage

kV

50/65

 

Rate Frequency

Hz

50/60

 

Rated Current

A

1250

 

Rated Short-time Withstand Current

kA

16

 

Rated Duration of Short-circuit

s

3

 

Rated Peak Withstand Current

kA

40

 

Rated Short-circuit Making Current

kA

40

 

Rated Short-circuit Breaking Current

kA

16

 

Max. Dc component

 

40%

 

Switch Operations of Rated Short-circuit Breaking Current

 

Operations

30

 

Rated Single Capacitor Bank Breaking Current

A

400

 

Rated Back-to-back Capacitor Bank Breaking Current

A

400

 

Mechanical Endurance

Operations

10000

 

Clearance Between Open Contacts

mm

16±1

 

Contact Closed Force Due to Bellows and Atmosphere

N

80±40

Counterforce of Contact at Full Stroke

N

140±40

Circuit Resistance at Min. Rated Contact Force

μΩ

≤30

Contact Limit Erosion 

mm

3

Mass of Moving Parts

kg

0.6

Internal Gas Pressure

Pa

<1.33×10-3

Shelf Life

Year

20

Rated Operating Sequence

O 0.3s - CO 180s CO

MECHANICAL DATA OF VACUUM SWITCH EQUIPPED WITH THE INTERRUPTERS

Data

Unit         

Value

Average Opening Speedfirst 6mm

m/s

1.4±0.2

Average Closing Speedlast 6mm

m/s

0.8±0.2              

Contact Bounce Duration at Closing Operation

ms

≤2

Out of Simultaneity of Contact Closing and Opening          

ms

≤1

Rated Contact Pressure

N

1800~2200

Max. rebound of contact at opening Operation

mm  

2

Overtravel during Opening

mm

≤2

Note  1 Rated characteristics to be given on request;

         2  Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-100 and GB1984-2003

         3. Within transformer oil or equivalent isolation medium

vacuum interrupter



Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.